Fine tuning – Boiler excess air
control
Furnace oil
Temp: Above 120 degC
Feed Water
Temp: 85 Deg C
Flue Gases
Temp: 247 Deg C
%O2; 11.8
%CO2: 6.7
CO: 1100 ppm
Boiler efficiency: 75.4%
Excess air:
120%
Dry Flue gas losses: 17.8%
Moisture losses: 5.2%
Radiation losses: 2 %
Blowdown losses: 0
Issues:
Very high Excess air (90-100%)
Very high flue gas temperature
Very high CO percentage
High FO temp
Before adjustment